Installation and
Safety Guidelines
Installation, Wiring,
and Specifications
2–49
Installation, Wiring, and Specifications
D0–08TR Relay Output
Outputs per module
8
Operating voltage range
6–27 VDC/6–240 VAC
Output type
Relay, form A, SPST
Peak voltage
30.0 VDC/264 VAC
Maximum current (resistive)
1 A/point, 4 A/common
Minimum load current
0.5 mA
Maximum leakage current
0.1 mA @ 264 VAC
ON voltage drop
N/A
ON voltage drop
N/A
Maximum inrush current
Output: 3 A for 10 ms
Common: 10 A for 10 ms
OFF to ON response
< 15 ms
ON to OFF response
< 10 ms
Status indicators
Module activity:
one green LED
Commons per module
2 isolated
(4 points/common)
Fuse
N/A
Fuse
N/A
Base power required (5 V)
Maximum 280 mA (all pts. ON)
Equivalent circuit
0
10
20
30
40
50 55
Ambient Temperature (
°
C/
°
F)
32
50
68
86
104
122 131
C
°
F
°
Derating Chart
Note: The DL05 must have firmware version V4.10 (or later) for this module to function properly.
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...