The For and Next instructions are used to
execute a section of ladder logic between
the For and Next instruction a specified
numbers of times. When the For
instruction is enabled, the program will
loop the specified number of times. If the
For instruction is not energized the section
of ladder logic between the For and Next
instructions is not executed.
For / Next instructions cannot be nested.
The normal I/O update and CPU
housekeeping is suspended while
executing the For / Next loop. The program
scan can increase significantly, depending
on the amount of times the logic between
the For and Next instruction is executed.
With the exception of immediate I/O
instructions, I/O will not be updated until
the program execution is completed for
that scan. Depending on the length of time
required to complete the program
execution, it may be necessary to reset the
watch dog timer inside of the For / Next
loop using the RSTWT instruction.
A aaa
FOR
NEXT
Operand Data Type
DL05 Range
A
aaa
V memory
V
All (See page 4–28)
Constant
K
1–9999
For / Next
(FOR)
(NEXT)
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...