PID Loop Operation
Maintenance
and T
roubleshooting
8–10
PID Loop Operation
The individual bit definitions of the PID Mode Setting 2 word (Addr+01) are listed in
the following table. Additional information about the use of this word is available later
in this chapter.
Bit
PID Mode Setting 2 Description
Read/Write
Bit=0
Bit=1
0
Input (PV) and Control Output Range
Unipolar/Bipolar select
(See Notes 1 and 2)
write
unipolar
bipolar
1
Input/Output Data Format select
(See Notes 1 and 2)
write
12 bit
15 bit
2
Analog Input filter
write
off
on
3
SP Input limit enable
write
disable
enable
4
Integral Gain (Reset) units select
write
seconds
minutes
5
Select Autotune PID algorithm
write
closed loop
open loop
6
Autotune selection
write
PID
PI only
(rate = 0)
7
Autotune start
read/write
autotune
done
force start
8
PID Scan Clock (internal use)
read
–
–
9
Input/Output Data Format 16-bit select
(See Notes 1 and 2)
write
not
16 bit
select
16 bit
10
Select separate data format for input and
output (See Notes 2, and 3)
write
same
format
separate
formats
11
Control Output Range
Unipolar/Bipolar select
(See Notes 2, and 3)
write
unipolar
bipolar
12
Output Data Format select
(See Notes 2, and 3)
write
12 bit
15 bit
13
Output data format 16-bit select
(See Notes 2, and 3)
write
not
16 bit
select
16 bit
14–15
Reserved for future use
–
–
–
Note 1: If the value in bit 9 is 0, then the values in bits 0 and 1 are read. If the value in
bit 9 is 1, then the values in bits 0 and 1 are not read, and bit 9 defines the
data format (the range is automatically unipolar).
Note 2: If the value in bit 10 is 0, then the values in bits 0, 1, and 9 define the input and
output ranges and data formats (the values in bits 11, 12, and 13 are not
read). If the value in bit 10 is 1, then the values in bits 0, 1, and 9 define only
the input range and data format, and bits 11, 12, and 13 are read and define
the output range and data format.
Note 3: If bit 10 has a value of 1 and bit 13 has a value of 0, then bits 11 and 12 are
read and define the output range and data format. If bit 10 and bit 13 each
have a value of 1, then bits 11 and 12 are not read, and bit 13 defines the data
format, (the output range is automatically unipolar).
PID Mode Setting 2
Bit Descriptions
(Addr + 01)
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...