PID Loop Operation
Maintenance
8–11
PID Loop Operation
The individual bit definitions of the Mode / Alarm monitoring (Addr+06) word is listed
in the following table. More details are in the PID Mode section and Alarms section.
Bit
Mode / Alarm Bit Description
Read/Write
Bit=0
Bit=1
0
Manual Mode Indication
read
–
Manual
1
Automatic Mode Indication
read
–
Auto
2
Cascade Mode Indication
read
–
Cascade
3
PV Input LOW–LOW Alarm
read
Off
On
4
PV Input LOW Alarm
read
Off
On
5
PV Input HIGH Alarm
read
Off
On
6
PV Input HIGH–HIGH Alarm
read
Off
On
7
PV Input YELLOW Deviation Alarm
read
Off
On
8
PV Input RED Deviation Alarm
read
Off
On
9
PV Input Rate-of-Change Alarm
read
Off
On
10
Alarm Value Programming Error
read
–
Error
11
Loop Calculation Overflow/Underflow
read
–
Error
12
Loop in Auto-Tune indication
read
Off
On
13
Auto-Tune error indication
read
–
Error
14–15
Reserved for Future Use
–
–
–
The individual bit definitions of the Ramp / Soak Table Flag (Addr+33) word is listed
in the following table. Further details are given in the Ramp / Soak Operation section.
Bit
Ramp / Soak Flag Bit Description
Read/Write
Bit=0
Bit=1
0
Start Ramp / Soak Profile
write
–
0
Õ
1 Start
1
Hold Ramp / Soak Profile
write
–
0
Õ
1 Hold
2
Resume Ramp / soak Profile
write
–
0
Õ
1
Resume
3
Jog Ramp / Soak Profile
write
–
0
Õ
1 Jog
4
Ramp / Soak Profile Complete
read
–
Complete
5
PV Input Ramp / Soak Deviation
read
Off
On
6
Ramp / Soak Profile in Hold
read
Off
On
7
Reserved
read
–
–
8–15
Current Step in R/S Profile
read
decode as byte (hex)
Bits 8–15 must be read as a byte to indicate the current segment number of the
Ramp/Soak generator in the profile. This byte will have the values 1, 2, 3, 4, 5, 6, 7, 8,
9, A, B, C, D, E, F, and 10, which represent segments 1 to 16 respectively. If the
byte=0, then the Ramp/Soak table is not active.
Mode / Alarm
Monitoring Word
(Addr + 06)
Ramp / Soak Table
Flags
(Addr + 33)
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...