CPU Specifications
and Operation
4–34
CPU Specifications and Operation
In
Direct
SOFT, choose the PLC menu, then Setup, then “Secondary Comm Port”.
S
Port:
From the port number list box at the top, choose “Port 2”.
S
Protocol:
Click the check box to the left of “MODBUS” (use AUX 56 on
the HPP, andselect “MBUS”), and then you’ll see the dialog box below.
Setup Communication Ports
Port:
Port 2
K-sequence
DirectNET
Non-sequence
MODBUS
Protocol:
Station Number:
1
Baud Rate:
38400
Close
Help
Timeout:
800 mS
RTS ON Delay Time:
5 mS
Stop Bits:
1
Parity:
None
RTS OFF Delay Time:
2 mS
S
Timeout:
amount of time the port will wait after it sends a message to get
a response before logging an error.
S
RTS ON / OFF Delay Time:
The RTS ON Delay Time specifies the time
the DL05 waits to send the data after it has raised the RTS signal line.
The RTS OFF Delay Time specifies the time the DL05 waits to release
the RTS signal line after the data has been sent.
When using the DL05 on
a multi-drop network, the RTS ON Delay time must be set to at least
5ms
and the RTS OFF Delay time must be set to at least
2ms
. If you
encounter problems, the time can be increased.
S
Station Number:
For making the CPU port a MODBUS
R
master, choose
“1”. The possible range for MODBUS slave numbers is from 1 to 247, but
the DL05 network instructions used in Master mode will access only
slaves 1 to 99. Each slave must have a unique number. At powerup, the
port is automatically a slave, unless and until the DL05 executes ladder
logic network instructions which use the port as a master. Thereafter, the
port reverts back to slave mode until ladder logic uses the port again.
S
Baud Rate:
The available baud rates include 300, 600, 1200, 2400,
4800, 9600, 19200, and 38400 baud. Choose a higher baud rate initially,
reverting to lower baud rates if you experience data errors or noise
problems on the network. Important: You must configure the baud rates of
all devices on the network to the same value. Refer to the appropriate
product manual for details.
S
Stop Bits:
Choose 1 or 2 stop bits for use in the protocol.
S
Parity:
Choose none, even, or odd parity for error checking.
Then click the button indicated to send the Port configuration to
the CPU, and click Close.
MODBUS Port
Configuration
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...