Drum Instruction
Programming
6–14
Drum Instruction Programming
The Event Drum (EDRUM) features time-based and event-based step transitions. It
operates according to the general principles of drum operation covered in the
beginning of this chapter. Below is the instruction as displayed by
Direct
SOFT.
1
Kdddd
EDRUM
CT
aa
Step Preset: K bb
0.01 sec/Count: K cccc
2
Kdddd
3
Kdddd
4
Kdddd
5
Kdddd
6
Kdddd
7
Kdddd
8
Kdddd
9
Kdddd
10
Kdddd
11
Kdddd
12
Kdddd
13
Kdddd
14
Kdddd
15
Kdddd
16
Kdddd
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
(Ffff)
Discrete Output Assignment
Counter Number
Step Preset
Timebase
Control
Inputs
Step Number
Counts per Step
Output Pattern
f
= Off,
F
= On
Start
Reset
Jog
Step # Counts Event
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Eeeee
Event per step
15
0
The Event Drum features 16 steps and 16 discrete outputs. Step transitions occur on
timed and/or event basis. The jog input also advances the step on each off-to-on
transition. Time is specified in counts per step, and events are specified as discrete
contacts. Unused steps and events must be left blank. The discrete output points
may be individually assigned.
Whenever the Start input is energized, the drum’s timer is enabled. As long as the
event is true for the current step, the timer runs during that step. When the step count
equals the counts per step, the drum transitions to the next step. This process stops
when the last step is complete, or when the Reset input is energized. The drum
enters the preset step chosen upon a CPU program-to-run mode transition, and
whenever the Reset input is energized.
Drum Parameters
Field
Data Types
Ranges
Counter Number
aa
–
0 – 174
Preset Step
bb
K
1 – 16
Timer base
cccc
K
0 – 99.99 seconds
Counts per step
dddd
K
0 – 9999
Event
eeee
X, Y, C, S, T, CT
see page 4–28
Discrete Outputs
ffff
X, Y, C
see page 4–28
Event Drum
(EDRUM)
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...