PID Loop Operation
Maintenance
8–3
PID Loop Operation
PID Loop Feature
Specifications
Number of loops
Selectable, 4 maximum
CPU V-memory needed
32 words (V locations) per loop selected, 64 words if using ramp/soak
PID algorithm
Position or Velocity form of the PID equation
Control Output polarity
Selectable direct-acting or reverse-acting
Error term curves
Selectable as linear, square root of error, and error squared
Loop update rate (time
between PID calculation)
0.05 to 99.99 seconds, user programmable
Minimum loop update rate
0.05 seconds for 1 to 4 loops,
Loop modes
Automatic, Manual (operator control), or Cascade control
Ramp/Soak Generator
Up to 8 ramp/soak steps (16 segments) per loop with indication of
ramp/soak step number
PV curves
Select standard linear, or square-root extract (for flow meter input)
Set Point Limits
Specify minimum and maximum setpoint values
Process Variable Limits
Specify minimum and maximum Process Variable values
Proportional Gain
Specify gains of 0.01 to 99.99
Integrator (Reset)
Specify reset time of 0.1 to 999.8 in units of seconds or minutes
Derivative (Rate)
Specify the derivative time from 0.01 to 99.99 seconds
Rate Limits
Specify derivative gain limiting from 1 to 20
Bumpless Transfer I
Automatically initialized bias and setpoint when control switches from
manual to automatic
Bumpless Transfer II
Automatically set the bias equal to the control output when control switches
from manual to automatic
Step Bias
Provides proportional bias adjustment for large setpoint changes
Anti-windup
For position form of PID, this inhibits integrator action when the control
output reaches 0% or 100 % (speeds up loop recovery when output
recovers from saturation)
Error Deadband
Specify a tolerance (plus and minus) for the error term (SP–PV), so that no
change in control output value is made
Alarm Feature
Specifications
Deadband
Specify 0.1% to 5% alarm deadband on all alarms
PV Alarm Points
Select PV alarm settings for Low–low, Low, High, and High-high conditions
PV Deviation
Specify alarms for two ranges of PV deviation from the setpoint value
Rate of Change
Detect when PV exceeds a rate of change limit you specify
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...