Installation, Wiring, and Specifications
2–8
Installation, Wiring, and Specifications
6. A good common ground reference (Earth ground) is essential for proper
operation of the DL05. One side of all control and power circuits and the
ground lead on flexible shielded cable must be properly connected to Earth
ground. There are several methods of providing an adequate common
ground reference, including:
a) Installing a ground rod as close to the panel as possible.
b) Connection to incoming power system ground.
7. Evaluate any installations where the ambient temperature may approach
the lower or upper limits of the specifications. If you suspect the ambient
temperature will not be within the operating specification for the DL05
system, measures such as installing a cooling/heating source must be
taken to get the ambient temperature within the range of specifications.
8. The DL05 systems are designed to be powered by 95-240 VAC or 12–24
VDC normally available throughout an industrial environment. Electrical
power in some areas where the PLCs are installed is not always stable and
storms can cause power surges. Due to this, powerline filters are
recommended for protecting the DL05 PLCs from power surges and
EMI/RFI noise. The Automation Powerline Filter, for use with 120 VAC and
240 VAC, 1–5 Amps, is an exellent choice (locate at
www.automationdirect.com), however, you can use a filter of your choice.
These units install easily between the power source and the PLC.
NOTE: If you are using other components in your system, make sure you refer to the
appropriate manual to determine how those units can affect mounting dimensions.
DL05 Micro PLCs can be secured to a panel by using mounting rails. We
recommend rails that conform to DIN EN standard 50 022. They are approximately
35mm high, with a depth of 7mm. If you mount the Micro PLC on a rail, do consider
using end brackets on each side of the PLC. The end bracket helps keep the PLC
from sliding horizontally along the rail, reducing the possibility of accidentally pulling
the wiring loose.
On the bottom of the PLC is a small retaining clip. To secure the PLC to a DIN rail,
place it onto the rail and gently push up on the clip to lock it onto the rail.
To remove the PLC, pull down on the retaining clip, lift up on the PLC slightly, then
pulling it away from the rail.
Using Mounting
Rails
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...