equal to
D
V
in
. The setting shall be smaller than
VDeadband
. Typically the inner
deadband can be set to 25-70% of the
VDeadband
value.
Vmax
: This setting gives the upper limit of permitted busbar voltage (see section
"Automatic voltage control for a single transformer"
VBase
. If
OVPartBk
is set to
Auto&ManBlock
, then busbar voltages above
Vmax
will
result in a partial blocking such that only lower commands are permitted.
Vmin
This setting gives the lower limit of permitted busbar voltage (see section
"Automatic voltage control for a single transformer"
VBase
. If
UVPartBk
is set to
Auto Block
or
Auto&ManBlock
, then busbar voltages
below
Vmin
will result in a partial blocking such that only raise commands are
permitted.
Vblock
: Voltages below
Vblock
normally correspond to a disconnected transformer and
therefore it is recommended to block automatic control for this condition (setting
UVBk
).
Vblock
is set in percent of
VBase
.
Time
t1Use
: Selection of time characteristic (definite or inverse) for
t1
.
t1
: Time delay for the initial (first) raise/lower command.
t2Use
: Selection of time characteristic (definite or inverse) for
t2
.
t2
: Time delay for consecutive raise/lower commands. In the circulating current
method, the second, third, etc. commands are all executed with time delay
t2
independently of which transformer in the parallel group that is tapping. In the master-
follower method with the follow tap option, the master is executing the second, third,
etc. commands with time delay
t2
. The followers on the other hand read the master’s
tap position, and adapt to that with the additional time delay given by the setting
tAutoMSF
and set individually for each follower.
t_MinTripDelay
: The minimum operate time when inverse time characteristic is used
(see section
Line voltage drop compensation (LDC)
OpertionLDC
: Sets the line voltage drop compensation function
Enabled
/
Disabled
.
OperCapaLDC
: This setting, if set
Enabled
, will permit the load point voltage to be
greater than the busbar voltage when line voltage drop compensation is used. That
situation can be caused by a capacitive load. When the line voltage drop compensation
function is used for parallel control with the reverse reactance method, then
OperCapaLDC
must always be set
Enabled
.
Section 14
1MRK 511 401-UUS A
Control
446
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...