13.2.3.2
Setting of common parameters
M13683-9 v9
Set the operation mode selector
Operation
to
Enabled
to release the fuse failure
function.
The voltage threshold
VPPU
is used to identify low voltage condition in the system.
Set
VPPU
below the minimum operating voltage that might occur during emergency
conditions. We propose a setting of approximately 70% of
VBase
.
The drop off time of 200 ms for dead phase detection makes it recommended to always
set
SealIn
to
Enabled
since this will secure a fuse failure indication at persistent fuse
fail when closing the local breaker when the line is already energized from the other
end. When the remote breaker closes the voltage will return except in the phase that
has a persistent fuse fail. Since the local breaker is open there is no current and the
dead phase indication will persist in the phase with the blown fuse. When the local
breaker closes the current will start to flow and the function detects the fuse failure
situation. But due to the 200 ms drop off timer the output BLKZ will not be activated
until after 200 ms. This means that distance functions are not blocked and due to the
“no voltage but current” situation might issue a trip.
The operation mode selector
OpModeSel
has been introduced for better adaptation to
system requirements. The mode selector enables selecting interactions between the
negative sequence and zero sequence algorithm. In normal applications, the
OpModeSel
is set to either
V2I2
for selecting negative sequence algorithm or
V0I0
for
zero sequence based algorithm. If system studies or field experiences shows that there
is a risk that the fuse failure function will not be activated due to the system conditions,
the dependability of the fuse failure function can be increased if the
OpModeSel
is set
to
V0I0 OR V2I2
or
OptimZsNs
. In mode
V0I0 OR V2I2
both negative and zero
sequence based algorithms are activated and working in an OR-condition. Also in
mode
OptimZsNs
both negative and zero sequence algorithms are activated and the one
that has the highest magnitude of measured negative or zero sequence current will
operate. If there is a requirement to increase the security of the fuse failure function
OpModeSel
can be selected to
V0I0 AND V2I2
which gives that both negative and zero
sequence algorithms are activated and working in an AND-condition, that is, both
algorithms must give condition for block in order to activate the output signals BLKV
or BLKZ.
13.2.3.3
Negative sequence based
M13683-17 v9
The relay setting value
3V2PU
is given in percentage of the base voltage
VBase
and
should not be set lower than the value that is calculated according to equation
Section 13
1MRK 511 401-UUS A
Secondary system supervision
296
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...