The same is applicable for slot 312-313 and slot 322-323.
DiffSync
defines the method of time synchronization for the line differential function:
Echo
or
GPS
.
Using
Echo
in this case is safe only if there is no risk of varying
transmission asymmetry.
GPSSyncErr
: when GPS synchronization is lost, synchronization of the line differential
function continues for 16 s based on the stability in the local IED clocks. After that,
setting
Block
blocks the line differential function or setting
Echo
keeps it on by using
the
Echo
synchronization method.
Using
Echo
in this case is safe only if there is no risk of varying
transmission asymmetry.
CommSync
defines the
Master
and
Slave
relation in the communication system, and
should not be mistaken for the synchronization of line differential current samples.
When direct fibre is used, one LDCM is set as
Master
and the other as
Slave
. When a
modem and multiplexer is used, the IED is always set as
Slave
because the
telecommunication system provides the clock master.
OptoPower
has two settings:
LowPower
is used for fibres 0 – 1 km (0.6 mile) and
HighPower
for fibres >1 km (>0.6 mile).
ComAlarmDel
defines the time delay for communication failure alarm. In
communication systems, route switching can sometimes cause interruptions with a
duration of up to 50 ms. Too short a time delay can thus cause nuisance alarms.
ComAlrmResDel
defines the time delay for communication failure alarm reset.
RedChSwTime
defines the time delay before switching over to a redundant channel in
case of primary channel failure.
RedChRturnTime
defines the time delay before switching back to the primary channel
after channel failure.
AsymDelay
denotes asymmetry which is defined as transmission delay minus receive
delay. If fixed asymmetry is known,
Echo
synchronization method can be used,
provided that
AsymDelay
is properly set. From the definition follows that asymmetry is
always positive at one end and negative at the other end.
1MRK 511 401-UUS A
Section 21
Remote communication
Bay control REC670 2.2 ANSI
599
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...