3.1.1.2
Description of configuration B30
M15200-12 v5
The configuration of the IED is shown in Figure
This configuration is used in double breaker arrangements.
Control, measuring and interlocking is fully configured, including communication with
other bays such as other lines and the bus coupler over GOOSE.
The following should be noted. The configuration is made with the binary input and
binary output boards in the basic IED delivery. In many cases this is sufficient, in other
cases e.g. with full control of all apparatuses included more IO cards are required. Our
proposal for a full version with control is to use two binary input modules and one or
two binary output modules. For systems without Substation Automation a second
binary output board might be required.
1MRK 511 401-UUS A
Section 3
Configuration
Bay control REC670 2.2 ANSI
55
Application manual