The data streams in the IED can be sent as unicast or as multicast. The user-defined IP
address set in the parameter
UDPDestAddress[x]
for each UDP stream defines if it is a
Unicast or Multicast. The address range 224.0.0.0 to 239.255.255.255 (Class D IP
addresses) is treated as multicast. Any other IP address outside this range is treated as
unicast and the UDP data will be only sent to that specific unicast IP address. In
addition to
UDPDestAddress[x]
parameter,
UDPDestPort[x]
parameter is used to
define the UDP destination port number for UDP client group[x].
In case of multicast IP, it will be the network switches and routers that take care of
replicating the packet to reach multiple receivers. Multicast mechanism uses network
infrastructure efficiently by requiring the IED to send a packet only once, even if it
needs to be delivered to a large number of receivers.
If there are more than one UDP client group defined as multicast, the user shall set
different multicast IP addresses for each UDP group.
The PMU clients receiving the UDP frames can also connect to the IED to request
(command frame) config frame 1, config frame 2, config frame 3, or header frame, and
to disable/enable real time data. This can be done by connecting to the TCP port
selected in
TCPportUDPdataCtrl[x]
for each UDP group. This connection is done
using TCP. The IED allows 4 concurrent client connections for every
TCPportUDPdataCtrl[x]
port (for each UDP client group[x]).
If the client tries to connect on
TCPportUDPdataCtrl[x
] port using a PMU-ID other
than what is configured for that PMUREPORT instance (
PMUReportUDP[x]
), then
that client is immediately disconnected and the
UDPCtrlCfgErrCnt
is incremented in
PMU Diagnostics on LHMI at
Main menu/Diagnostics/Communication/PMU
diagnostics/PMUSTATUS:1
Even if the parameter
SendDataUDP[x]
is set to
Disable
it is still possible for the
clients to connect on the TCP port and request the configuration frames.
6.2
Protocol reporting via IEEE 1344 and C37.118
PMUREPORT
GUID-0C45D2FA-1B95-4FCA-B23B-A28C2770B817 v1
6.2.1
Identification
GUID-0090956B-48F1-4E8B-9A40-90044C71DF20 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Protocol reporting via IEEE 1344 and
C37.118
PMUREPORT
-
-
1MRK 511 401-UUS A
Section 6
Wide area measurement system
Bay control REC670 2.2 ANSI
105
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...