Operate
Angle1(2)
Power1(2)
P
Q
en06000441.vsd
IEC06000441 V1 EN-US
Figure 87:
Underpower mode
The setting
Power1(2)
gives the power component pick up value in the
Angle1(2)
direction. The setting is given in p.u. of the generator rated power, see equation
Minimum recommended setting is 0.2% of S
N
when metering class CT inputs into the
IED are used.
N
S
3 VBase IBase
=
×
×
EQUATION2047 V1 EN-US
(Equation 73)
The setting
Angle1(2)
gives the characteristic angle giving maximum sensitivity of the
power protection function. The setting is given in degrees. For active power the set
angle should be 0° or 180°. 0° should be used for generator low forward active power
protection.
Section 8
1MRK 511 401-UUS A
Current protection
218
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...