ANSI09000171_1_en.vsd
SESRSYN (25)
MENMODE
INTONE
PSTO
SWPOSN
NAME1
NAME2
OFF
DL
DB
DLB
SLGGIO
NAME3
NAME4
ANSI09000171 V1 EN-US
Figure 107:
Selection of the energizing direction from a local HMI symbol through a
selector switch function block.
14.1.3
Application examples
M12323-3 v7
The synchronism check function block can also be used in some switchyard
arrangements, but with different parameter settings. Below are some examples of how
different arrangements are connected to the IED analog inputs and to the function
block SESRSYN, 25. One function block is used per circuit breaker.
The input used below in example are typical and can be changed by use
of configuration and signal matrix tools.
The SESRSYN and connected SMAI function block instances must
have the same cycle time in the application configuration.
Section 14
1MRK 511 401-UUS A
Control
310
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...