Mode
: The voltage and current used for the power measurement. The setting
possibilities are shown in table
.
Table 27:
Complex power calculation
Set value
Mode
Formula used for complex power calculation
A,B,C
*
*
*
A
B
C
A
B
C
S V
I
V
I
V
I
=
×
+
×
+
×
EQUATION2038 V1 EN-US
(Equation 77)
Arone
*
*
A
C
AB
BC
S V
I
V
I
=
×
×
-
EQUATION2039 V1 EN-US
(Equation 78)
PosSeq
*
PosSeq
PosSeq
S 3 V
I
= ×
×
EQUATION2040 V1 EN-US
(Equation 79)
A,B
*
A
B
AB
*
S
V
(I
I
)
=
×
-
EQUATION2041 V1 EN-US
(Equation 80)
B,C
*
B
C
BC
*
S
V
(I
I
)
=
×
-
EQUATION2042 V1 EN-US
(Equation 81)
C,A
*
C
A
CA
*
S
V
(I
I
)
=
×
-
EQUATION2043 V1 EN-US
(Equation 82)
A
*
A
A
S 3 V
I
= ×
×
EQUATION2044 V1 EN-US
(Equation 83)
B
*
B
B
S 3 V
I
= ×
×
EQUATION2045 V1 EN-US
(Equation 84)
C
*
C
C
S 3 V
I
= ×
×
EQUATION2046 V1 EN-US
(Equation 85)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
Enabled
/
Disabled
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is larger than the set pick up power value
Power1(2)
1MRK 511 401-UUS A
Section 8
Current protection
Bay control REC670 2.2 ANSI
223
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...