Control operation can be performed from the local IED HMI. If users are defined in the
IED, then the local/remote switch is under authority control, otherwise the default user
can perform control operations from the local IED HMI without logging in. The default
position of the local/remote switch is on remote.
Accepted originator categories for PSTO
If the requested command is accepted by the authority control, the value will change.
Otherwise the attribute
blocked-by-switching-hierarchy
is set in the
cause
signal. If the
PSTO value is changed during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in
.
Table 33:
Accepted originator categories for each PSTO
Permitted Source To Operate
Originator (orCat)
0 = Off
4,5,6
1 = Local
1,4,5,6
2 = Remote
2,3,4,5,6
3 = Faulty
4,5,6
4 = Not in use
4,5,6
5 = All
1,2,3,4,5,6
6 = Station
2,4,5,6
7 = Remote
3,4,5,6
PSTO = All, then it is no priority between operator places. All operator places are
allowed to operate.
According to IEC 61850 standard the
orCat
attribute in originator category are defined
Table 34:
orCat attribute according to IE C61850
Value
Description
0
not-supported
1
bay-control
2
station-control
3
remote-control
4
automatic-bay
5
automatic-station
6
automatic-remote
7
maintenance
8
process
1MRK 511 401-UUS A
Section 14
Control
Bay control REC670 2.2 ANSI
355
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...