If there is no second busbar B at the other side of the transformer and therefore no 489
disconnector, then the state for 489 is set to open by setting the appropriate module
inputs as follows:
•
489_OP = 1
•
489_CL = 0
14.4.5
Interlocking for bus-section breaker A1A2_BS (3)
IP14154-1 v2
14.4.5.1
Application
M15110-3 v7
The interlocking for bus-section breaker (A1A2_BS ,3) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure
can be used for different busbars, which includes a bus-section circuit breaker.
WA1 (A1)
289
489G
189
389G
WA2 (A2)
en04000516_ansi.vsd
289G
189G
A1A2_BS
152
ANSI04000516 V1 EN-US
Figure 142:
Switchyard layout A1A2_BS (3)
M15111-4 v3
The signals from other bays connected to the module A1A2_BS are described below.
14.4.5.2
Signals from all feeders
M15111-6 v4
If the busbar is divided by bus-section circuit breakers into bus-sections and both
circuit breakers are closed, the opening of the circuit breaker must be blocked if a bus-
coupler connection exists between busbars on one bus-section side and if on the other
bus-section side a busbar transfer is in progress:
Section 14
1MRK 511 401-UUS A
Control
386
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...