IR
IED pickup current (U>Trip/SeriesResistor)
Ires
is the current through the voltage limiter and
ΣImag
is the sum of the magnetizing currents from all CTs in the circuit (for example, 4 for
restricted earth fault protection, 2 for reactor differential protection, 3-5 for autotransformer
differential protection).
It should be remembered that the vectorial sum of the currents must be used (IEDs,
Metrosil and resistor currents are resistive). The current measurement is insensitive to
DC component in fault current to allow the use of only the AC components of the fault
current in the above calculations.
The voltage dependent resistor (Metrosil) characteristic is shown in Figure
Series resistor thermal capacity
SEMOD54734-336 v6
The series resistor is dimensioned for 200 W. Care shall be exercised while testing to
ensure that if current needs to be injected continuously or for a significant duration of
time, check that the heat dissipation Vxxx Series Resistance value does not exceed 200
W. Otherwise injection time shall be reduced to the minimum.
1MRK 511 401-UUS A
Section 7
Differential protection
Bay control REC670 2.2 ANSI
133
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...