IMinx
: Minimum pickup current for step
x
in % of
IBase
. Set
IMinx
below
Pickupx
for
every step to achieve ANSI reset characteristic according to standard. If
IMinx
is set
above
Pickupx
for any step the ANSI reset works as if current is zero when current
drops below
IMinx
.
txMin
: Minimum trip time for all inverse time characteristics. At high currents the
inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting. Setting
range: 0.000 - 60.000s in steps of 0.001s.
MultPUx
: Multiplier for scaling of the current setting value. If a binary input signal
ENMULTx (enableMultiplier) is activated the current operation level is increased by
this setting constant. Setting range: 1.0-10.0
ANSI10000058-1-en.vsdx
Trip time
Pickup current
tx
txMin
ANSI10000058 V1 EN-US
Figure 60:
Minimum pickup current and trip time for inverse time characteristics
In order to fully comply with the definition of the curve, the setting parameter
txMin
shall be set to a value equal to the operating time of the selected inverse curve for
twenty times the set current pickup value. Note that the operate time is dependent on
the selected time multiplier setting
kx
.
ResetTypeCrvx
: The reset of the delay timer can be made as shown in Table
.
Section 8
1MRK 511 401-UUS A
Current protection
158
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...