then be stopped, and instead the timer,
t1 3Ph
, for three-pole auto reclosing will be
started from zero. The sequence will continue as a three-pole auto reclosing sequence,
if it is a selected alternative reclosing mode. The second fault which can be single-
phase is tripped three-pole because the trip function (SMPPTRC) in the IED has an
evolving fault timer which ensures that second fault is always tripped three-pole. For
other types of relays where the relays do not include this function, the
PREP3PH
output (or the inverted
PERMIT1PH
output) is used to prepare the other sub-system for
three-phase tripping. This signal will, for evolving fault situations, be activated a short
time after the first trip has reset and will thus ensure that new starts (trips) will be three
phase.
14.2.2.21
Automatic continuation of the auto reclosing sequence
M12391-223 v5
The auto recloser can be programmed to proceed to the next auto reclosing shots (if
multiple shots are selected) even if start signals are not received from protection
functions, but the circuit breaker is still not closed. This is done by setting
AutoCont
=
Enabled
and
tAutoContWait
to the required delay for the function to proceed without a
new start.
14.2.2.22
Thermal overload protection holding the auto recloser back
M12391-226 v3
If the
THOLHOLD
input (thermal overload protection holding auto reclosing back) is
activated, it will keep the auto recloser on a hold until it is reset. There may thus be a
considerable delay between start of the auto recloser and the breaker closing command
to the circuit breaker. An external logic limiting the time and sending an inhibit to the
INHIBIT
input can be used. The input can also be used to set the auto recloser on hold
for a longer or shorter period.
14.2.3
Setting guidelines
IP14929-1 v1
14.2.3.1
Configuration
M12399-3 v3
Use the PCM600 configuration tool to configure signals.
Auto recloser function parameters are set via the local HMI or Parameter Setting Tool
(PST). Parameter Setting Tool is a part of PCM600.
Recommendations for input signals
M12399-7 v10
Please see Figure
and default factory configuration for
examples.
Section 14
1MRK 511 401-UUS A
Control
336
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...