Lock-out
RXMD1
11
12
21
MAIN ZAK CLOSE
CLOSE COMMAND
SMBO
OR
SMBRREC (79)
OR
CCRBRF (50BF)
BJ-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
TRBU
ANSI05000315_2_en.vsd
SET
RESET
ELECTRICAL RESET
RELAY
ANSI05000315 V2 EN-US
Figure 115:
Lock-out arranged with an external lock-out relay
CLOSE COMMAND
OR
SMBRREC (79)
OR
CCRBRF (50BF)
BJ-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
BJTRIP
ANSI05000316_2_en.vsd
SMPPTRC (94)
SMBO
AND
RESET LOCK-OUT
OR
OR
SESRSYN (25)
SOFTWARE
OR IO RESET
AUTO STOP
MAN ENOK
MAN CLOSE
SMBRREC (79) CLOSE
SETLKOUT
CLLOUT
RSTLOUT
ANSI05000316 V2 EN-US
Figure 116:
Lock-out arranged with internal logic with manual closing going through
in IED
14.2.2.20
Evolving fault
M12391-217 v4
An evolving fault starts as a single-phase fault which leads to single-pole tripping and
then the fault spreads to another phase. The second fault is then cleared by three-pole
tripping.
The auto recloser will first receive a start signal (
START
) without any three-phase
signal (
TR3P
). The auto recloser will start a single-phase auto reclosing sequence, if
programmed to do so. At the evolving fault clearance there will be a new
START
signal
and three-phase trip information,
TR3P
. The single-phase auto reclosing sequence will
1MRK 511 401-UUS A
Section 14
Control
Bay control REC670 2.2 ANSI
335
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...