A double breaker arrangement requires two function blocks, one for breaker
WA1_QA1 and one for breaker WA2_QA1. No voltage selection is necessary, because
the voltage from busbar 1 VT is connected to V3PB1 on SESRSYN for WA1_QA1
and the voltage from busbar 2 VT is connected toV3PB1 on SESRSYN for
WA2_QA1. The voltage from the line VT is connected to V3PL1 on both function
blocks. The condition of VT fuses shall also be connected as shown in figure
. The
voltage selection parameter
CBConfig
is set to
No voltage sel.
for both function blocks.
14.1.3.5
Breaker-and-a-half
M12330-3 v8
Figure
describes a breaker-and-a-half arrangement with three SESRSYN functions
in the same IED, each of them handling voltage selection for WA1_QA1, TIE_QA1
and WA2_QA1 breakers respectively. The voltage from busbar 1 VT is connected to
V3PB1 on all three function blocks and the voltage from busbar 2 VT is connected to
V3PB2 on all three function blocks. The voltage from line1 VT is connected to V3PL1
on all three function blocks and the voltage from line2 VT is connected to V3PL2 on
all three function blocks. The positions of the disconnectors and VT fuses shall be
connected as shown in Figure
1MRK 511 401-UUS A
Section 14
Control
Bay control REC670 2.2 ANSI
315
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...