8.2.3.2
Setting example
GUID-20729467-24AB-42F0-9FD1-D2959028732E v1
Directional phase overcurrent protection, four steps can be used in different ways,
depending on the application where the protection is used. A general description is
given below.
The pickup current setting of the inverse time protection, or the lowest current step of
the definite time protection, must be defined so that the highest possible load current
does not cause protection operation. The protection reset current must also be
considered so that a short peak of overcurrent does not cause the operation of a
protection even when the overcurrent has ceased. This phenomenon is described in
Figure
Pickup current
Current I
The IED does not reset
Line phase current
Time t
Reset current
ANSI09000146-en-1.vsd
ANSI09000146 V1 EN-US
Figure 61:
Pickup and reset current for an overcurrent protection
The lowest setting value can be written according to Equation
Section 8
1MRK 511 401-UUS A
Current protection
160
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...