Setting procedure on the IED
The parameters for the frequency time accumulation protection FTAQFVR (81A) are
set using the local HMI or through the dedicated software tool in Protection and
Control Manager (PCM600).
Common base IED values for primary current
IBase
and primary voltage
VBase
are set
in the global base values for settings function GBASVAL. The
GlobalBaseSel
is used
to select GBASVAL for the reference of base values.
FTAQFVR (81A) used to protect a turbine:
Frequency during start-up and shutdown is normally not calculated, consequently the
protection function is blocked by CB position, parameter
CBCheck
enabled. If the
generator supply any load when CB is in open position e.g. excitation equipment and
auxiliary services this may be considered as normal condition and
CBCheck
is ignored
when the load current is higher then the set value of
PickupCurrentLevel
. Set the
current level just above minimum load.
EnaVoltCheck
set to
Disable
.
tCont
: to be coordinated to the grid requirements.
tAccLimit
,
FreqHighLimit
and
FreqLowLimit
setting is derived from the turbine
manufacturer's operating requirements, note that
FreqLowLimit
setting must always be
lower than the set value of
FreqHighLimit
.
FTAQFVR (81A) used to protect a generator:
Frequency during start-up and shutdown is normally not calculated, consequently the
protection function is blocked by CB position, parameter
CBCheck
enabled.
PickupCurrentLevel
set to
Disable
.
EnaVoltCheck
set to
Enable
, voltage and frequency limits set according to the
generators manufacturer's operating requirements. Voltage and frequency settings
should also be coordinated with the pickup values for over and underexcitation
protection.
tCont
: to be coordinated to the grid requirements.
tAccLimit
,
FreqHighLimit
and
FreqLowLimit
setting is derived from the generator
manufacturer's operating requirements.
1MRK 511 401-UUS A
Section 10
Frequency protection
Bay control REC670 2.2 ANSI
267
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...