15.1.3.6
Intertrip scheme
M13869-62 v5
Set
Operation
=
Enabled
Set
SchemeType
=
Intertrip
Set
tCoord
= 50 ms (10 ms + maximal transmission time)
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
Set
tSecurity
= 0.015 s
15.2
Current reversal and Weak-end infeed logic for
distance protection 3-phase ZCRWPSCH (85)
IP15751-1 v4
15.2.1
Identification
M15073-1 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for distance protection 3-phase
ZCRWPSCH
-
85
15.2.2
Application
IP15023-1 v1
15.2.2.1
Current reversal logic
M13895-4 v6
To avoid this kind of disturbances, a fault current reversal logic (transient blocking
logic) can be used.
The unwanted operations that might occur can be explained by looking into Figure
. Initially the protection A2 at A side will detect a fault in forward
direction and send a communication signal to the protection B2 at remote end, which is
measuring a fault in reverse direction.
Section 15
1MRK 511 401-UUS A
Scheme communication
474
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...