The setting
ConnectionType
: Connection type for that specific instance (n) of the
SMAI (if it is
Ph-N
or
Ph-Ph
). Depending on connection type setting the not connected
Ph-N
or
Ph-Ph
outputs will be calculated as long as they are possible to calculate. E.g.
at
Ph-Ph
connection A, B and C will be calculated for use in symmetrical situations. If
N component should be used respectively the phase component during faults I
N
/V
N
must be connected to input 4.
Negation
: If the user wants to negate the 3ph signal, it is possible to choose to negate
only the phase signals
Negate3Ph
, only the neutral signal
NegateN
or both
Negate3Ph
+N
. negation means rotation with 180° of the vectors.
GlobalBaseSel
: Selects the global base value group used by the function to define
(
IBase
), (
VBase
) and (
SBase
).
MinValFreqMeas
: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of VBase (for each instance n).
Settings
DFTRefExtOut
and
DFTReference
shall be set to default value
InternalDFTRef
if no VT inputs are available.
Even if the user sets the
AnalogInputType
of a SMAI block to
“
Current
”, the
MinValFreqMeas
is still visible. However, using the
current channel values as base for frequency measurement is
not
recommendable
for a number of reasons, not last among them being
the low level of currents that one can have in normal operating
conditions.
Examples of adaptive frequency tracking
Preprocessing block shall only be used to feed functions within the
same execution cycles (e.g. use preprocessing block with cycle 1 to
feed transformer differential protection). The only exceptions are
measurement functions (CVMMXN, CMMXU,VMMXU, etc.) which
shall be fed by preprocessing blocks with cycle 8.
When two or more preprocessing blocks are used to feed one protection
function (e.g. over-power function GOPPDOP), it is of outmost
importance that parameter setting DFTReference has the same set value
for all of the preprocessing blocks involved
Section 23
1MRK 511 401-UUS A
Basic IED functions
616
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...