1. PMUREPORT
2. PHASORREPORT
3. ANALOGREPORT
4. BINARYREPORT
Each category has its corresponding parameter settings except for BINARYREPORT
function block which does not have any specific parameters and settings.
1. PMUREPORT is the main function block which controls the operation of other
PMU reporting function blocks. Each instance of PMUREPORT function block
has the following parameters:
•
Operation
: Enables/Disables the operation of the corresponding instance of
PMU reporting functionality by choosing
On
/
Off
setting.
•
SvcClass
: It refers to the 1-byte SVC_CLASS field of the configuration
frame 3 (CFG-3) organization defined in IEEE C37.118.2 message format.
Here the user can select the performance class (service class) used for
synchrophasor data measurement according to IEEE C37.118.1 standard.
The options are
P class
or
M class
.
Note:
There are 2 PMUREPORT instances available (PMUREPORT:1 and
PMUREPORT:2) corresponding to 2 independent data streams. The user can
set different or identical service class for each data stream. In case of
different service classes, special rules shall be considered in PCM600 ACT
for the connection of preprocessor blocks (SMAI) and 3PHSUM blocks to
PHASORREPORT blocks. More details are available under section
Report Function Blocks Connection Rules in PCM600 Application
Configuration Tool (ACT)
•
Global_PMU_ID
: It refers to the 16-byte G_PMU_ID field of the
configuration frame 3 (CFG-3) organization defined in IEEE C37.118.2
message format. It is a 16-character (128 bits) user-assigned value which can
be sent with the configuration 3 message. It allows uniquely identifying
PMUs in a system that has more than 65535 PMUs. The coding for the 16
bytes is left to the user for assignment.
•
PMUdataStreamIDCODE
: It refers to the 2-byte IDCODE field of the
configuration frame and data frame organization defined in IEEE C37.118.2
message format. It is a user assigned ID number (1-65534) for each data
stream sent out from the PMU. This is especially important when having
multiple data streams (multiple PMU functionality).
Note:
The data stream IDCODE is a unique code for each and every data
stream in one physical PMU device. In the IED, there are 2 PMUREPORT
instances available (PMUREPORT:1 and PMUREPORT:2) corresponding to
2 independent data streams. The user must set different IDCODEs for each
instance.
•
PhasorFormat
: It refers to the Bit 0 of the FORMAT field of the
configuration frames 1, 2 and 3 organization defined in IEEE C37.118.2
message format. Here the user can select the format of the calculated
Section 6
1MRK 511 401-UUS A
Wide area measurement system
122
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...