en04000499_ansi.vsd
189OPTR (bay 1/sect.A1)
S1DC_OP
VPS1_DC
EXDU_BB
AND
189OPTR (bay n/sect.A1)
. . .
. . .
. . .
VP189TR (bay 1/sect.A1)
VP189TR (bay n/sect.A1)
EXDU_DB (bay 1/sect.A1)
EXDU_DB (bay n/sect.A1)
. . .
. . .
. . .
. . .
. . .
. . .
AND
AND
ANSI04000499 V1 EN-US
Figure 153:
Signals from double-breaker bays in section A1 to a bus-section
disconnector
For a bus-section disconnector, these conditions from the A2 busbar section are valid:
en04000500_ansi.vsd
189OPTR (bay 1/sect.A2)
S2DC_OP
VPS2_DC
EXDU_BB
AND
189OPTR (bay n/sect.A2)
. . .
. . .
. . .
VP189TR (bay 1/sect.A2)
VP189TR (bay n/sect.A2)
EXDU_DB (bay 1/sect.A2)
EXDU_DB (bay n/sect.A2)
. . .
. . .
. . .
. . .
. . .
. . .
AND
AND
ANSI04000500 V1 EN-US
Figure 154:
Signals from double-breaker bays in section A2 to a bus-section
disconnector
For a bus-section disconnector, these conditions from the B1 busbar section are valid:
1MRK 511 401-UUS A
Section 14
Control
Bay control REC670 2.2 ANSI
395
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...