17.5.3
Setting guidelines
IP14841-1 v1
M12811-3 v3
The input parameters for the Event function (EVENT) can be set individually via the
local HMI (
Main Menu/Settings / IED Settings / Monitoring / Event Function
) or
via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
M12811-5 v3
The inputs can be set individually as:
•
NoEvents
•
OnSet
, at pick-up of the signal
•
OnReset
, at drop-out of the signal
•
OnChange
, at both pick-up and drop-out of the signal
•
AutoDetect
, the EVENT function makes the reporting decision (reporting criteria
for integers have no semantic, prefer to be set by the user)
LONChannelMask or SPAChannelMask
M12811-15 v2
Definition of which part of the event function block that shall generate events:
•
Disabled
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
MinRepIntVal (1 - 16)
M12811-29 v3
A time interval between cyclic events can be set individually for each input channel.
This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that
is, no cyclic communication.
M12811-34 v1
It is important to set the time interval for cyclic events in an optimized
way to minimize the load on the station bus.
17.6
Disturbance report DRPRDRE
IP14584-1 v2
1MRK 511 401-UUS A
Section 17
Monitoring
Bay control REC670 2.2 ANSI
531
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...