t
1
tMin
D
=
EQUATION1848 V2 EN-US
(Equation 117)
Where:
DA
absolute voltage deviation from the set point
D
relative voltage deviation in respect to set deadband value
For the last equation, the condition
t1 > tMin
shall also be fulfilled. This practically
means that
tMin
will be equal to the set
t1
value when absolute voltage deviation DA is
equal to ΔV ( relative voltage deviation D is equal to 1). For other values see
figure
. It should be noted that operating times, shown in the figure
are for 30,
60, 90, 120, 150 & 180 seconds settings for
t1
and 10 seconds for
tMin
.
t1=180
t1=150
t1=120
t1=90
t1=60
t1=30
IEC06000488_2_en.vsd
IEC06000488 V2 EN-US
Figure 171:
Inverse time characteristic for TR1ATCC (90) and TR8ATCC (90)
The second time delay,
t2
, will be used for consecutive commands (commands in the
same direction as the first command). It can have a definite or inverse time
characteristic according to the setting
t2Use
(Constant/Inverse). Inverse time
characteristic for the second time delay follows the similar formulas as for the first
time delay, but the
t2
setting is used instead of
t1
.
Section 14
1MRK 511 401-UUS A
Control
414
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...