46 Start-up
21
RPDO21-EV time
Defines the event time (time-out time) for the
Rx PDO21 in the asynchronous transmission
mode. If the Rx PDO21 communication
between the adapter module and the bus
master fails, the adapter module sets the
communication between the module and the
drive to the off-line mode.
Event timer (time-out timer) elapses as a
multiple of 1 ms of the entry of this parameter.
Note:
The time-out supervision is activated
upon a successful reception of an Rx PDO21.
0
=
Disable
0
= Disable
Time-out supervision is disabled.
1…65535 (ms)
Event time in ms.
No. Name/Value
Description
Default
setting