Communication profiles 101
2
OFF3_
CONTROL
1
Continue operation (OFF3 inactive).
0
Emergency stop; stop within time
defined with the drive parameter.
Proceed to
OFF3 ACTIVE
; proceed to
SWITCH-ON INHIBITED
.
Warning:
Ensure motor and driven
machine can be stopped using this stop
mode.
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION ENABLED
.
Note:
Run enable signal must be
active; see the drive manuals. If the
drive is set to receive the Run enable
signal from the fieldbus, this bit
activates the signal.
0
Inhibit operation; proceed to
OPERATION INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation; proceed to
RFG:
OUTPUT ENABLED
.
0
Force the Ramp Function Generator
output to zero. The drive ramps to stop
(current and DC voltage limits in force).
5
RAMP_HOLD
1
Enable the ramp function;
proceed to
RFG: ACCELERATOR
ENABLED
.
0
Halt ramping (the Ramp Function
Generator output held).
6
RAMP_IN_
ZERO
1
Normal operation; proceed to
OPERATION
.
Note:
Effective only if the fieldbus
interface is set as the source for this
signal with drive parameters.
0
Force the Ramp Function Generator
input to zero.
Control word of ABB Drives profile
Bit
Name
Value STATE/Description
Содержание FCAN-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FCAN 01 CANopen adapter module User s manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 30: ...30 Mechanical installation ...
Страница 36: ...36 Electrical installation ...
Страница 81: ...Start up 81 ...
Страница 82: ...82 Start up 8 Configure the FCAN 01 properties Select the node boot up sequence ...
Страница 108: ...108 Communication profiles ...
Страница 152: ...152 Communication protocol ...
Страница 156: ...156 Diagnostics ...
Страница 160: ...160 Technical data ...
Страница 164: ...164 Appendix A Dictionary structure and entries ...
Страница 173: ...Appendix B CANopen error codes 173 FFFF Manufacturer specific Error code hex Meaning ...
Страница 174: ...174 Appendix B CANopen error codes ...