Start-up 63
5108 FBA PAR 8
(RPDO1-TR TYPE)
255
2)
Asynchronous
transmission
mode is used by Rx PDO1.
5110 FBA PAR 10
(TPDO1-COB-ID)
1
(= Default)
Tx PDO1 is enabled and
configured to use the default
COB-ID.
5111 FBA PAR 11
(TPDO1-TR TYPE)
255
Asynchronous transmission
mode is used by Tx PDO1.
Transmission is triggered by the
event time.
5112 FBA PAR 12
(TPDO1-EV TIME)
100
2)
Event time, that is, event time
elapses every 100 ms.
5401 FBA DATA IN 1
5
(= Act1 16bit)
Actual value 1 as mapping
entry 2 in Tx PDO1
5402 FBA DATA IN 2
6
(= Act2 16bit)
Actual value 2 as mapping
entry 3 in Tx PDO1
5403 FBA DATA IN 3
106
Signal 106 POWER as mapping
entry 4 in Tx PDO1
5501 FBA DATA OUT 1
2
(= Ref1 16bit)
Reference 1 as mapping entry 2
in Rx PDO1
5502 FBA DATA OUT 2
3
(= Ref2 16bit)
Reference 2 as mapping entry 3
in Rx PDO1
5503 FBA DATA OUT 3
135
Signal 135 COMM VALUE 1 as
mapping entry 4 in Rx PDO1
5127 FBA PAR
REFRESH
1
= REFRESH
Activates the fieldbus
configuration parameter
settings.
9904 MOTOR CTRL
MODE
2
= VECTOR: TORQ
Selects the motor control mode.
1001 EXT1
COMMANDS
10
= COMM
Communication module as the
source for the start, stop and
direction commands in EXT1
mode
1002 EXT2
COMMANDS
10
= COMM
Communication module as the
source for the start, stop and
direction commands in EXT2
mode
Drive parameter
Setting for ACS355
drives
Description
Содержание FCAN-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FCAN 01 CANopen adapter module User s manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 30: ...30 Mechanical installation ...
Страница 36: ...36 Electrical installation ...
Страница 81: ...Start up 81 ...
Страница 82: ...82 Start up 8 Configure the FCAN 01 properties Select the node boot up sequence ...
Страница 108: ...108 Communication profiles ...
Страница 152: ...152 Communication protocol ...
Страница 156: ...156 Diagnostics ...
Страница 160: ...160 Technical data ...
Страница 164: ...164 Appendix A Dictionary structure and entries ...
Страница 173: ...Appendix B CANopen error codes 173 FFFF Manufacturer specific Error code hex Meaning ...
Страница 174: ...174 Appendix B CANopen error codes ...