Start-up 39
FCAN-01 configuration parameters – group A (group 1)
Note:
The actual parameter group number depends on the drive
type. Group A (group 1) corresponds to:
•
parameter group
51
in ACS355, ACSM1 and ACS850
•
parameter group
51
in ACS880 if the adapter is installed as
fieldbus adapter A or group
54
if the adapter is installed as
fieldbus adapter B.
No. Name/Value
Description
Default
setting
01
FBA TYPE
Read-only.
Shows the fieldbus adapter type as
detected by the drive. Value cannot be adjusted
by the user.
If the value is 0 = None, the communication
between the drive and the module has not been
established.
1
=
CAN-
open
02
Node ID
Selects the node address of the module.
Each device on the CANopen network must
have a unique node identifier. Used to define a
node identifier for the drive it is connected to.
3
1…127
Node address
Содержание FCAN-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FCAN 01 CANopen adapter module User s manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 30: ...30 Mechanical installation ...
Страница 36: ...36 Electrical installation ...
Страница 81: ...Start up 81 ...
Страница 82: ...82 Start up 8 Configure the FCAN 01 properties Select the node boot up sequence ...
Страница 108: ...108 Communication profiles ...
Страница 152: ...152 Communication protocol ...
Страница 156: ...156 Diagnostics ...
Страница 160: ...160 Technical data ...
Страница 164: ...164 Appendix A Dictionary structure and entries ...
Страница 173: ...Appendix B CANopen error codes 173 FFFF Manufacturer specific Error code hex Meaning ...
Страница 174: ...174 Appendix B CANopen error codes ...