![ABB ACS550-01 Скачать руководство пользователя страница 83](http://html.mh-extra.com/html/abb/acs550-01/acs550-01_user-manual_2977083.webp)
ACS550 User’s Manual
83
Start-Up
35 =
COMM
– Energize relay based on input from fieldbus communication.
• Fieldbus writes binary code in parameter 0134 that can energize relay 1…relay 6 according to the following:
• 0 = De-energize relay, 1 = Energize relay.
36 =
COMM
(-1) – Energize relay based on input from fieldbus communication.
• Fieldbus writes binary code in parameter 0134 that can energize relay 1…relay 6 according to the following:
• 0 = De-energize relay, 1 = Energize relay.
37 =
TIMER
FUNCTION
1 – Energize relay when Timer Function 1 is active. See Group 36, Timer Functions.
38…40 =
TIMER
FUNCTION
2…4 – Energize relay when Timer Function 2…4 is active. See Timer Function 1 above.
41 =
M
.
TRIG
FAN
– Energize relay when cooling fan counter is triggered. See Group 29, Maintenance Trig.
42 =
M
.
TRIG
REV
– Energize relay when revolutions counter is triggered. See Group 29, Maintenance Trig.
43 =
M
.
TRIG
RUN
– Energize relay when run time counter is triggered. See Group 29, Maintenance Trig.
44 =
M
.
TRIG
MWH
– Energize relay when MWh counter is triggered. See Group 29, Maintenance Trig.
45 =
RESERVED
– Relay is not used and is de-energized.
1402
RELAY OUTPUT 2
Defines the event or condition that activates relay 2 – what relay output 2 means.
• See 1401
RELAY
OUTPUT
1.
1403
RELAY OUTPUT 3
Defines the event or condition that activates relay 3 – what relay output 3 means.
• See 1401
RELAY
OUTPUT
1.
1404
RO 1 ON DELAY
Defines the switch-on delay for relay 1.
• On / off delays are ignored when relay output 1401 is set to PFC.
1405
RO 1 OFF DELAY
Defines the switch-off delay for relay 1.
• On / off delays are ignored when relay output 1401 is set to PFC.
1406
RO 2 ON DELAY
Defines the switch-on delay for relay 2.
• See
RO
1
ON
DELAY
.
1407
RO 2 OFF DELAY
Defines the switch-off delay for relay 2.
• See
RO
1
OFF
DELAY
.
1408
RO 3 ON DELAY
Defines the switch-on delay for relay 3.
• See
RO
1
ON
DELAY
.
Code Description
Par. 0134
Binary
RO6
RO5 RO4 RO3 RO2 RO1
0
000000
0
0
0
0
0
0
1
000001
0
0
0
0
0
1
2
000010
0
0
0
0
1
0
3
000011
0
0
0
0
1
1
4
000100
0
0
0
1
0
0
5…62
…
…
…
…
…
…
…
63
111111
1
1
1
1
1
1
Par. 0134 Binary
RO6
RO5 RO4 RO3 RO2 RO1
0
000000
1
1
1
1
1
1
1
000001
1
1
1
1
1
0
2
000010
1
1
1
1
0
1
3
000011
1
1
1
1
0
0
4
000100
1
1
1
0
1
1
5…62
…
…
…
…
…
…
…
63
111111
0
0
0
0
0
0
1404
ON
DELAY
1405
OFF
DELAY
Control event
Relay status