ACS550 User’s Manual
Installation
•
For installations involving ACS550-U1, frame sizes R5 or R6 and IP 54 / UL type
12 enclosures: A punch for creating conduit mounting holes.
•
For installations involving ACS550-U1, frame size R6: The appropriate crimping
tool for power cable lugs. See "Power Terminal Considerations – R6 Frame Size".
•
Mounting hardware: screws or nuts and bolts, four each. The type of hardware
depends on the mounting surface and the frame size:
Suitable Environment and Enclosure
Confirm that the site meets the environmental requirements. To prevent damage
prior to installation, store and transport the drive according to the environmental
requirements specified for storage and transportation. See "Ambient Conditions"
on
page
240.
Confirm that the enclosure is appropriate, based on the site contamination level:
•
IP 21 / UL type 1 enclosure. The site must be free of airborne dust, corrosive
gases or liquids, and conductive contaminants such as condensation, carbon
dust, and metallic particles.
•
IP 54 / UL type 12 enclosure. This enclosure provides protection from airborne
dust and light sprays or splashing water from all directions.
Suitable Mounting Location
Confirm that the mounting location meets the following constraints:
•
The drive must be mounted vertically on a smooth, solid surface, and in a suitable
environment as defined above.
•
The minimum space requirements for the drive are the outside dimensions (see
"Outside Dimensions" on page
238), plus air flow space around the unit (see
on page
•
The distance between the motor and the drive is limited by the maximum motor
cable length. See either "Motor Connection Specifications"
on page
Cable Requirements for CE & C-Tick Compliance" on page 226.
•
The mounting site must support the drive’s modest weight. See "Weight" on page
239.
Frame Size
Mounting Hardware
R1…R4
M5
#10
R5
M6
1/4 in
R6
M8
5/16 in