Embedded Fieldbus
Fault 28 – Serial 1 Err
If the drive’s control panel shows fault code 28 “
SERIAL
1
ERR
”, check for either of the
following:
•
The master system is down. To correct, resolve problem with master system.
•
The communication connection is bad. To correct, check communication
connection at the drive.
•
The time-out selection for the drive is too short for the given installation. The
master is not polling the drive within the specified time-out delay. To correct,
increase the time set by parameter 3019
COMM
FAULT
TIME
.
Faults 31…33 – EFB1…EFB3
The three EFB fault codes listed for the drive in "Diagnostics" starting on page 200
(fault codes 31…33) are not used.
Intermittent Off-line Occurrences
The problems described above are the most common problems encountered with
ACS550 serial communication. Intermittent problems might also be caused by:
•
Marginally loose connections,
•
Wear on wires caused by equipment vibrations,
•
Insufficient grounding and shielding on both the devices and on the
communication cables.