ACS550 User’s Manual
Start-Up
1209
TIMED MODE SEL
Defines timer activated, constant speed mode. Timer can be used to change between external reference and a
maximum of three constant speeds, or to change between a maximum of 4 selectable speeds, i.e. constant speeds
1, 2, 3 and 4.
1 =
EXT
/
CS
1/2/3 – Selects an external speed when no timer is active, selects Constant speed 1 when Timer 1 is
active, Selects Constant speed 2 when Timer 2 is active and selects Constant speed 3 when both Timers 1 and 2
are active.
2 =
CS
1/2/3/4 – Selects Constant speed 1 when no timer is active, selects Constant speed 2 when Timer 1 is active,
selects Constant speed 3 when Timer 2 is active, selects Constant speed 4 when both timers are active.
Code Description
TIMER
1
TIMER
2
Function
0
0
External reference
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
TIMER
1
TIMER
2
Function
0
0
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
0
1
Constant speed 3 (1204)
1
1
Constant speed 4 (1205)