ACS550 User’s Manual
235
Technical Data
Analog Cables
Recommendations for analog signal runs:
•
Use double shielded, twisted pair cable.
•
Use one individually shielded pair for each signal.
•
Do not use a common return for different analog signals.
Digital Cables
Recommendation for digital signal runs: A double shielded cable is the best
alternative, but single-shielded, twisted, multi-pair cable is also usable.
Control Panel Cable
If the control panel is connected to the drive with a cable, use only Category 5 Patch
ethernet cable. The maximum length that is tested to meet EMC specifications is 3 m
(9.8 ft). Longer cables are susceptible to electromagnetic noise and must be user-
tested to verify that EMC requirements are met. Where long runs are required
(especially for runs longer than about 12 m (40 ft)), use a RS232/RS485 converter at
each end and run RS485 cable.
Drive’s Control Connection Terminals
The following table provides specifications for the drive’s control terminals
Efficiency
Approximately 98% at nominal power level.
Cooling
Air Flow, 208…240 Volt Drives
The following table lists heat loss and air flow data for 208…240 Volt drives.
Frame Size
Control
Maximum Wire Size
Torque
mm
2
AWG
Nm
lb-ft
All
1.5
16
0.4
0.3
Cooling Specifications
Method
Internal fan, flow direction from bottom to top.
Requirement
Free space above and below the ACS550 drive: 200 mm (8 in).
Free space is not required on the drive’s sides – ACS550 units can be mounted side-
by-side.
Drive
Heat Loss
Air Flow
ACS550-x1-
Frame Size
W
BTU/Hr
m
3
/h
ft
3
/min
-04A6-2
R1
55
189
44
26
-06A6-2
R1
73
249
44
26