ACS550 User’s Manual
Diagnostics
31
EFB
1
Fault code reserved for the embedded fieldbus (EFB) protocol application.
The meaning is protocol dependent.
32
EFB
2
33
EFB
3
34
MOTOR
PHASE
Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
35
OUTPUT
WIRING
Possible power wiring error detected. When the drive is not running it
monitors for an improper connection between the drive input power and the
drive output. Check for and correct:
• Proper input wiring – line voltage is NOT connected to drive output.
• The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023
WIRING
FAULT
.
36
INCOMP
SWTYPE
The drive cannot use the software.
• Internal Fault.
• The loaded software is not compatible with the drive.
• Call support representative.
101
SERF
CORRUPT
Error internal to the drive. Contact your local ABB sales representative and
report the error number.
102
RESERVED
103
SERF
MACRO
104
RESERVED
105
RESERVED
201
DSP
T
1
OVERLOAD
Error in the system. Contact your local ABB sales representative and report
the error number.
202
DSP
T
2
OVERLOAD
203
DSP
T
3
OVERLOAD
204
DSP
STACK
ERROR
205
RESERVED
(
OBSOLETE
)
206
OMIO
ID
ERROR
207
EFB
LOAD
ERROR
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action