118
ACS550 User’s Manual
Start-Up
3611
STOP TIME 3
Defines timer 3 daily stop time.
• See parameter 3603
3612
START DAY 3
Defines timer 3 weekly start day.
• See parameter 3604
3613
STOP DAY 3
Defines timer 3 weekly stop day.
• See parameter 3605
3614
START TIME 4
Defines timer 4 daily start time.
• See parameter 3602
3615
STOP TIME 4
Defines timer 4 daily stop time.
• See parameter 3603
3616
START DAY 4
Defines timer 4 weekly start day.
• See parameter 3604
3617
STOP DAY 4
Defines timer 4 weekly stop day.
• See parameter 3605
3622
BOOSTER SEL
Selects the source for the booster signal.
0 =
NOT
SEL
– Booster
signal is disabled.
1 =
DI
1 – Defines DI1 as the booster signal.
2…6 =
DI
2…
DI
6 – Defines DI2…DI6 as the booster signal.
-1 =
DI
1(
INV
) – Defines an inverted digital input DI1 as the booster signal.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input DI2…DI6 as the booster signal.
3623
BOOSTER TIME
Defines the booster ON time. Time is started when booster sel
signal is released. If parameter range is 01:30:00, then booster
is active for 1 hour and 30 minutes after activation DI is
released.
3626
TIMER FUNC1 SRC
Defines the time periods used by the timer.
0 =
NOT
SEL
– No time periods have been selected.
1 = P1 – Time Period1 selected in the timer.
2 = P2 – Time Period2 selected in the timer.
3 = P2 + P1 – Time Periods 1 and 2 selected in the timer.
4 = P3 – Time Period3 selected in the timer.
5 = P3 + P1 – Time Periods 1 and 3 selected in the timer.
6 = P3 + P2 – Time Periods 2 and 3 selected in the timer.
7 = P3 + P2 + P1 – Time Periods 1, 2 and 3 selected in the timer.
8 = P4 – Time Period4 selected in the timer.
9 = P4 + P1 – Time Periods 4 and 1 selected in the timer.
10 = P4 + P2 – Time Periods 4 and 2 selected in the timer.
Code Description
Booster active
Activation DI
Booster time