130
ACS550 User’s Manual
Start-Up
4232
CORRECTION SRC
Defines the trimming reference for the correction source.
1 =
PID
2
REF
– Uses appropriate
REF
MAX
(S
WITCH
A
OR
B):
• 1105
REF
1
MAX
when
REF
1 is active (A).
• 1108
REF
2
MAX
when
REF
2 is active (B).
2 =
PID
2
OUTPUT
– Uses the absolute maximum speed or frequency (Switch C):
• 2002
MAXIMUM
SPEED
if 9904
MOTOR
CONTROL
MODE
= 1
SPEED
or 2
TORQUE
.
• 2008
MAXIMUM
FREQUENCY
IF
9904
MOTOR
CONTROL
MODE
= 3
SCALAR
.
Code Description
Switch
Mul.
Mul.
+
Select
Add
X
X
(par. 4232)
Trimmed ref
PID2 ref
Select
(par. 4230)
Ext ref 1 max (A)
Ext ref 2 max (B)
Abs Max Speed
Ramped ref
off
propor.
direct
trim scale
PID 2
Trimming PID2 out
Trimming PID2 ref
Freq (C)