![ABB ACS550-01 Скачать руководство пользователя страница 61](http://html.mh-extra.com/html/abb/acs550-01/acs550-01_user-manual_2977061.webp)
ACS550 User’s Manual
61
Start-Up
4012
SETPOINT
MIN
-500.0%…500.0%
0.1%
0%
4013
SETPOINT
MAX
-500.0%…500.0%
0.1%
100%
4014
FBK
SEL
1…10
-
1
4015
FBK
MULTIPLIER
-32.768…32.767 (0 = not used)
0.001
0
4016
ACT
1
INPUT
1…2
-
2
9
4017
ACT
2
INPUT
1…2
-
2
9
4018
ACT
1
MINIMUM
-1000…1000%
1%
0%
4019
ACT
1
MAXIMUM
-1000…1000%
1%
100%
4020
ACT
2
MINIMUM
-1000…1000%
1%
0%
4021
ACT
2
MAXIMUM
-1000…1000%
1%
100%
4022
SLEEP
SELECTION
0…7, -1…-6
-
0
4023
PID
SLEEP
LEVEL
0…7200 rpm / 0.0…120 Hz
1 rpm / 0.1 Hz 0 Hz
4024
PID
SLEEP
DELAY
0.0…3600 s
0.1 s
60 s
4025
WAKE
-
UP
DEV
Unit and scale defined by par. 4006 and
4007
1
-
4026
WAKE
-
UP
DELAY
0…60 s
0.01 s
0.50 s
4027
PID
1
PARAM
s
ET
-6…11
1
0
Group 41: Process PID Set 2
4101
GAIN
0.1…100
0.1
1.0
4102
INTEGRATION
TIME
0.0s =
NOT
SEL
, 0.1…3600 s
0.1 s
60 s
4103
DERIVATION
TIME
0…10 s
0.1 s
0 s
4104
PID
DERIV
FILTER
0…10 s
0.1 s
1 s
4105
ERROR
VALUE
INV
0 =
NO
, 1 =
YES
-
0
4106
UNITS
0…31
-
4
4107
UNIT
SCALE
0…4
1
1
4108
0%
VALUE
Unit and scale defined by par. 4106 and
4107
1
0.0%
4109
100%
VALUE
Unit and scale defined by par. 4106 and
4107
1
100%
4110
SET
POINT
SEL
0…19
1
1
9
4111
INTERNAL
SETPNT
Unit and scale defined by par. 4106 and
4107
1
40.0%
4112
SETPOINT
MIN
-500.0%…500.0%
0.1%
0%
4113
SETPOINT
MAX
-500.0%…500.0%
0.1%
100%
4114
FBK
SEL
1…10
-
1
4115
FBK
MULTIPLIER
-32.768…32.767 (0 =
NOT
USED
)
0.001
0
4116
ACT
1
INPUT
1…5
-
2
9
4117
ACT
2
INPUT
1…5
-
2
9
4118
ACT
1
MINIMUM
-1000…1000%
1%
0%
4119
ACT
1
MAXIMUM
-1000…1000%
1%
100%
4120
ACT
2
MINIMUM
-1000…1000%
1%
0%
4121
ACT
2
MAXIMUM
-1000…1000%
1%
100%
4122
SLEEP
SELECTION
0…7, -1…-6
-
0
4123
PID
SLEEP
LEVEL
0…7200 rpm / 0.0…120 Hz
1 rpm / 0.1 Hz 0 Hz
4124
PID
SLEEP
DELAY
0.0…3600 s
0.1 s
60 s
Code
Name
Range
Resolution
Default
User
S