ACS550 User’s Manual
165
Embedded Fieldbus
The following table summarizes the 4xxxx drive control registers 40001…40099 (for
4xxxx registers above 40099, see the drive parameter list, e.g. 40102 is parameter
0102):
Modbus Register
Access
Remarks
4
0001
CONTROL
WORD
R/W
Maps directly to the profile‘
S
CONTROL
WORD
. Supported only
if 5305 = 0 or 2 (ABB Drives profile). Parameter 5319 holds
a copy in hex format.
4
0002
Reference 1
R/W
Range = 0…+20000 (scaled to 0…1105
REF
1
MAX
), or
-20000…0 (scaled to 1105
REF
1
MAX
…0).
4
0003
Reference 2
R/W
Range = 0…+10000 (scaled to 0…1108
REF
2
MAX
), or
-10000…0 (scaled to 1108
REF
2
MAX
…0).
4
0004
STATUS
WORD
R
Maps directly to the profile‘
S
STATUS
WORD
. Supported only if
5305 = 0 or 2 (ABB Drives profile). Parameter 5320 holds a
copy in hex format.
4
0005
Actual 1
(select using 5310)
R
By default, stores a copy of 0103
OUTPUT
FREQ
. Use
parameter 5310 to select a different actual value for this
register.
4
0006
Actual 2
(select using 5311)
R
By default, stores a copy of 0104
CURRENT
. Use parameter
5311 to select a different actual value for this register.
4
0007
Actual 3
(select using 5312)
R
By default, stores nothing. Use parameter 5312 to select an
actual value for this register.
4
0008
Actual 4
(select by 5313)
R
By default, stores nothing. Use parameter 5313 to select an
actual value for this register.
4
0009
Actual 5
(select using 5314)
R
By default, stores nothing. Use parameter 5314 to select an
actual value for this register.
4
0010
Actual 6
(select using 5315)
R
By default, stores nothing. Use parameter 5315 to select an
actual value for this register.
4
0011
Actual 7
(select using 5316)
R
By default, stores nothing. Use parameter 5316 to select an
actual value for this register.
4
0012
Actual 8
(select using 5317)
R
By default, stores nothing. Use parameter 5317 to select an
actual value for this register.
4
0031
ACS550
CONTROL
WORD
LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0301.
4
0032
ACS550
CONTROL
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0302.
4
0033
ACS550
STATUS
WORD
LSW
R
Maps directly to the Least Significant Word of the DCU
profile‘s
STATUS
WORD
. Supported only if 5305 = 1.
See parameter 0303.
4
0034
ACS550
STATUS
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile‘s
STATUS
WORD
. Supported only if 5305 = 1.
See parameter 0304.