ACS550 User’s Manual
65
Start-Up
Complete Parameter Descriptions
This section describes the actual signals and parameters for ACS550.
Group 99: Start-up Data
This group defines special Start-up data required to:
•
Set up the drive.
•
Enter motor information.
Code Description
9901
LANGUAGE
Selects the display language.
9902
APPLIC MACRO
Selects an application macro. Application macros automatically edit parameters to configure the ACS550 for a
particular application.
9904
MOTOR CTRL MODE
Selects the motor control mode.
1 =
VECTOR
: s
PEED
– sensorless vector control mode.
• Reference 1 is speed reference in rpm.
• Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
MAXIMUM
SPEED
, or 2001
MINIMUM
SPEED
if the absolute value of the minimum speed is greater than the maximum
speed).
2 =
VECTOR
:
TORQ
.
• Reference 1 is speed reference in rpm.
• Reference 2 is torque reference in % (100% is nominal torque.)
3 =
SCALAR
:
SPEED
– scalar control mode.
• Reference 1 is frequency reference in Hz.
• Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008
MAXIMUM
FREQUENCY
, or 2007
MINIMUM
FREQUENCY
if the absolute value of the minimum speed is greater
than the maximum speed).
9905
MOTOR NOM VOLT
Defines the nominal motor voltage.
• Must equal the value on the motor rating plate.
• The ACS550 cannot supply the motor with a voltage greater than the
mains voltage.
9906
MOTOR NOM CURR
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
• Range allowed: (0.2…2.0) · I
2hd
(where I
2hd
is drive current).
9907
MOTOR NOM FREQ
Defines the nominal motor frequency.
• Range: 10…500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals the
MOTOR
NOM
VOLT
.
• Field weakening point = Nom Freq * Supply Volt / Mot Nom Volt
0 =
ENGLISH
1 =
ENGLISH
(
AM
)
2 =
DEUTSCH
3 =
ITALIANO
4 =
ESPAÑOL
5 =
PORTUGUES
6 =
NEDERLANDS
7 =
FRANCAIS
8 =
DANSK
9 =
SUOMI
10 =
SVENSKA
11 =
RUSSKI
12 =
POLSKI
13 =
TÜRKCE
1 =
ABB
STANDARD
2 = 3-
WIRE
3 =
ALTERNATE
4 =
MOTOR
POT
5 =
HAND
/
AUTO
6 =
PID
CONTROL
7 =
PFC
CONTROL
8 =
TORQUE
CTRL
0 =
USER
S
1
LOAD
-1 =
USER
S
1
SAVE
-2 =
USER
S
2
LOAD
-3 =
USER
S
2
SAVE
Output voltage
Output
P 9907
frequency
P 9905