216
ACS550 User’s Manual
Technical Data
Ratings, 380…480 Volt Drives
Abbreviated column headers are described in “Symbols” on page 216.
1. Not available in ACS550-U1 series.
2. Not available in ACS550-01 series.
Symbols
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current. Also note that:
•
The ratings apply for ambient temperature of 40 °C (104 °F).
•
The maximum allowed motor shaft power is limited to 1.5 ·
P
hd
.
If the limit is
exceeded, motor torque and current are automatically restricted. The function
protects the input bridge of the drive against overload.
Type Code
Normal Use
Heavy-Duty Use
Frame
Size
ACS550-x1-
see below
I
2N
A
P
N
kW
P
N
HP
I
2hd
A
P
hd
kW
P
hd
HP
Three-phase supply voltage,
380
…
480 V
-03A3-4
3.3
1.1
1.5
2.4
0.75
1
R1
-04A1-4
4.1
1.5
2
3.3
1.1
1.5
R1
-05A4-4
5.4
2.2
Note 1
4.1
1.5
Note 1
R1
-06A9-4
6.9
3
3
5.4
2.2
2
R1
-08A8-4
8.8
4
5
6.9
3
3
R1
-012A-4
11.9
5.5
7.5
8.8
4
5
R1
-015A-4
15.4
7.5
10
11.9
5.5
7.5
R2
-023A-4
23
11
15
15.4
7.5
10
R2
-031A-4
31
15
20
23
11
15
R3
-038A-4
38
18.5
25
31
15
20
R3
-044A-4
44
22
30
38
18.5
25
R4
-059A-4
59
30
40
44
22
30
R4
-072A-4
72
37
50
59
30
40
R4
-077A-4
77
Note 2
60
65
Note 2
50
R5
-096A-4
96
45
75
77
37
60
R5
-124A-4
124
55
100
96
45
75
R6
-157A-4
157
75
125
124
55
100
R6
-180A-4
180
90
150
156
75
125
R6
-195A-4
195
110
Note 1
162
90
Note 1
R6
Typical ratings:
Normal use
(10% overload capability)
I
2N
continuous rms current. 10% overload is allowed for one minute in ten minutes.
P
N
typical motor power in normal use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The Horsepower ratings apply to most 4-pole NEMA motors.
Heavy-duty use
(50% overload capability)
I
2hd
continuous rms current. 50% overload is allowed for one minute in ten minutes.
P
hd
typical motor power in heavy duty use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The Horsepower ratings apply to most 4-pole NEMA motors.