ACS550 User’s Manual
223
Technical Data
Drive’s Power Connection Terminals
The following table provides specifications for the drive’s power connection
terminals.
1. Do not use aluminum cable with frame sizes R1…R4.
Power Terminal Considerations – R6 Frame Size
Warning! For R6 power terminals, if
compression lugs are supplied, they can only
be used for wire sizes that are 95 mm
2
(3/0
AWG) or larger. Smaller wires will loosen and
may damage the drive, and require ring lugs as
described below.
Ring Lugs
On the R6 frame size, if the cable size used is less
than 95 mm
2
(3/0 AWG) or if no compression lugs
are supplied, use ring lugs according to the following procedure.
1. Select appropriate ring lugs from the following table.
2. Attach the supplied terminal lugs to the drive end of the cables.
3. Isolate the ends of the ring lugs with insulating tape or shrink tubing.
4. Attach terminal lug to the drive.
Frame
Size
U1, V1, W1
U2, V2, W2
BRK+, UDC+ Terminals
Earthing PE Terminal
Min. Wire Size
Max. Wire Size
Torque
Max. Wire Size
Torque
mm
2
AWG
mm
2
AWG
Nm
lb-ft
mm
2
AWG
Nm
lb-ft
R1
1
0.75
18
16
6
1.3
1
16
6
1.3
1
R2
1
0.75
18
16
6
1.3
1
16
6
1.3
1
R3
1
2.5
14
25
3
2.7
2
25
3
2.7
2
R4
1
10
8
50
1/0
5.6
4
50
1/0
5.6
4
R5
16
6
70
2/0
15
11
70
2/0
15
11
R6
95
3/0
185
350 MCM
40
30
185
350 MCM
40
30
Wire Size
Manufacturer
Ring Lug
Crimping
Tool
No. of
Crimps
mm
2
kcmil/
AWG
16
6
Burndy
YAV6C-L2
MY29-3
1
Ilsco
CCL-6-38
ILC-10
2
25
4
Burndy
YA4C-L4BOX
MY29-3
1
Ilsco
CCL-4-38
MT-25
1
X60002
2
3
4