ACS550 User’s Manual
205
Diagnostics
Faults that indicate conflicts in the parameter settings are listed below.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action
1000
PAR
HZRPM
Parameter values are inconsistent. Check for any of the following:
• 2001
MINIMUM
SPEED
> 2002
MAXIMUM
SPEED
.
• 2007
MINIMUM
FREQ
> 2008
MAXIMUM
FREQ
.
• 2001
MINIMUM
SPEED
/ 9908
MOTOR
NOM
SPEED
is outside proper range
(> 50)
• 2002
MAXIMUM
SPEED
/ 9908
MOTOR
NOM
SPEED
is outside proper range
(> 50)
• 2007
MINIMUM
FREQ
/ 9907
MOTOR
NOM
FREQ
is outside proper range
(> 50)
• 2008
MAXIMUM
FREQ
/ 9907
MOTOR
NOM
FREQ
is outside proper range
(> 50)
1001
PAR
PFCREFNG
Parameter values are inconsistent. Check for the following:
• 2007
MINIMUM
FREQ
is negative, when 8123
PFC
ENABLE
is active.
1003
PAR
AI
SCALE
Parameter values are inconsistent. Check for any of the following:
• 1301
AI
1
MIN
> 1302
AI
1
MAX
.
• 1304
AI
2
MIN
> 1305
AI
2
MAX
.
1004
PAR
AO
SCALE
Parameter values are inconsistent. Check for any of the following:
• 1504
AO
1
MIN
> 1505
AO
1
MAX
.
• 1510
AO
2
MIN
> 1511
AO
2
MAX
.
1005
PAR
PCU
2
Parameter values for power control are inconsistent: Improper motor
nominal kVA or motor nominal power. Check for the following:
• 1.1 < (9906
MOTOR
NOM
CURR
* 9905
MOTOR
NOM
VOLT
* 1.73 / P
N
) < 3.0
• Where: P
N
= 1000 * 9909
MOTOR
NOM
POWER
(if units are kW)
or P
N
= 746 * 9909
MOTOR
NOM
POWER
(if units are HP, e.g. in US)
1006
PAR
EXTROMISSING
Parameter values are inconsistent. Check for the following:
• Extension relay module not connected and
• 1410…1412
RELAY
OUTPUTS
4…6 have non-zero values.
1007
PAR
FBUSMISSING
Parameter values are inconsistent. Check for and correct:
• A parameter is set for fieldbus control (e.g. 1001
EXT
1
COMMANDS
= 10
(
COMM
)), but 9802
COMM
PROT
SEL
= 0.
1008
PAR
PFCWOSCALAR
Parameter values are inconsistent – 9904
MOTOR
CTRL
MODE
must be = 3
(
SCALAR
:
SPEED
), when 8123
PFC
ENABLE
is activated.
1009
PAR
PCU
1
Parameter values for power control are inconsistent: Improper motor
nominal frequency or speed. Check for both of the following:
• 1 < (60 * 9907
MOTOR
NOM
FREQ
/ 9908
MOTOR
NOM
SPEED
< 16
• 0.8 < 9908
MOTOR
NOM
SPEED
/
(120 * 9907
MOTOR
NOM
FREQ
/ Motor Poles) < 0.992
1012
PAR
PFC
IO
1
IO configuration is not complete – not enough relays are parameterized to
PFC. Or, a conflict exists between Group 14, parameter 8117,
NR
OF
AUX
MOT
, and parameter 8118,
AUTOCHNG
INTERV
.
1013
PAR
PFC
IO
2
IO configuration is not complete – the actual number of PFC motors
(parameter 8127,
MOTORS
) does not match the PFC motors in Group 14
and parameter 8118
AUTOCHNG
INTERV
.
1014
PAR
PFC
IO
3
IO configuration is not complete – the drive is unable to allocate a digital
input (interlock) for each PFC motor (parameters 8120
INTERLOCKS
and
8127
MOTORS
).