![ABB ACS550-01 Скачать руководство пользователя страница 117](http://html.mh-extra.com/html/abb/acs550-01/acs550-01_user-manual_2977117.webp)
ACS550 User’s Manual
117
Start-Up
Code Description
3601
TIMERS ENABLE
Selects the source for the timer enable signal.
0 = NOT SEL – Timed functions are disabled.
1 = DI1– Defines digital input DI1 as the timed function enable signal.
• The digital input must be activated to enable the timed function.
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the timed function enable signal.
7 = ENABLED – Timed functions are enabled.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the timed function enable signal.
• This digital input must be de-activated to enable the timed function.
• -2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the timed function enable signal.
3602
START TIME 1
Defines the daily start time.
• The time can be changed in steps of 2 seconds.
• If parameter value is 07:00:00, then the timer is
activated at 7 a.m.
• The figure shows multiple timers on different
weekdays.
3603
STOP TIME 1
Defines the daily stop time.
• The time can be in steps of 2 seconds.
• If the parameter value is 09:00:00, then the timer is deactivated at 9 a.m.
3604
START DAY 1
Defines the weekly start day.
1 = Monday
…
7 = Sunday.
• If parameter value is 1, then timer 1 weekly is active from Monday midnight (00:00:00).
3605
STOP DAY 1
Defines weekly stop day.
1 = Monday
…
7 = Sunday.
• If parameter value is 5, then timer 1 weekly is deactivated on Friday midnight (23:59:58).
3606
START TIME 2
Defines timer2 daily start time.
• See parameter 3602
3607
STOP TIME 2
Defines timer2 daily stop time.
• See parameter 3603
3608
START DAY 2
Defines timer 2 weekly start day.
• See parameter 3604
3609
STOP DAY 2
Defines timer 2 weekly stop day.
• See parameter 3605
3610
START TIME 3
Defines timer 3 daily start time.
• See parameter 3602
Mon Tue Wed Thu Fri Sat Sun
00:00:00
09:00:00
10:30:00
12:00:00
13:00:00
15:00:00
17:00:00
20:30:00